ESS-GRID DyniO is a high-efficiency, high-reliability all-in-one battery system developed mainly for small and medium-sized energy storage microgrids, supporting photovoltaic access, containing EMS, and off-grid switching device, supporting parallel operation of multiple units, supporting oil-engine hybrid operation, and supporting fast switching work between on- and off-grid.
It is applicable to a variety of scenarios such as small industrial and commercial, small island microgrids, farms, villas, battery laddering utilization, etc. to meet the needs of different users.
Product Features
ALL -IN-ONE ESS
Over 6000 cycles @ 90% DOD
Low standby power consumption ≤15W, no-load operation loss less than 100W
Add as many battery modules as needed
Support seamless switching between parallel and off-grid (less than 5ms)
The noise level of the whole machine is less than 20dB
Built-in Hybird Inverter, BMS, EMS, Battery bank
Multiple Power & Capacity Combinations
Supports AC-side expansion
The AC side of the All in One ESS supports 3 units in parallel or off-grid operation, and the maximum power can reach 90kW.
| Battery Parameters | |||||
| Battery Model | HV PACK 8 | HV PACK 9 | HV PACK 10 | HV PACK11 | HV PACK12 |
| Number Of Battery Packs | 8 | 9 | 10 | 11 | 12 |
| Rated Voltage (V) | 460.8 | 518.4 | 576 | 633.6 | 691.2 |
| Voltage Range (V) | 410.4 -511.2 | 461.7-575.1 | 513.0-639.0 | 564.3-702.9 | 615.6-766.8 |
| Rated Energy (kWh) | 62.4 | 69.9 | 77.7 | 85.5 | 93.3 |
| Max. Discharging Current (A) | 67.5 | ||||
| Cycle Life | 6000 Cycles @90% DOD | ||||
| PV Parameter | |||||
| Inverter Model | INV C30 | ||||
| Maximum Power | 19.2kW+19.2kW | ||||
| Maximum PV Voltage | 850V | ||||
| PV Starting Voltage | 250V | ||||
| MPPT Voltage Range | 200V-830V | ||||
| Maximum PV Current | 32A+32A | ||||
| AC Side (Grid-connected) | |||||
| Rated Power | 30kVA | ||||
| Rated Current | 43.5A | ||||
| Rated Grid Voltage | 400V/230V | ||||
| Grid Voltage Range | -20%~15% | ||||
| Voltage Frequency Range | 50Hz/47Hz~52Hz | ||||
| 60Hz/57Hz~62Hz | |||||
| Voltage Harmonics | <5% (>30% Load) | ||||
| Power Factor | -0.8~0.8 | ||||
| AC Side (Off-grid) | |||||
| Rated Output Power | 30kVA | ||||
| Maximum Output Power | 33kVA | ||||
| Rated Output Current | 43.5A | ||||
| Maximum Output Current | 48A | ||||
| Rated Voltage | 400V/230V | ||||
| Unbalance | <3% (Resistive Load) | ||||
| Output Voltage Harmonics | 1 | ||||
| Frequency Range | 50/60Hz | ||||
| Output Overload (Current) | 48A<I load ≤54A/100S 54A<I load ≤65A/100S |
||||
| System Parameters | |||||
| Communication Por | EMS:RS485 Battery: CAN/RS485 | ||||
| DIDO | DI: 2-way DO: 2-way | ||||
| Maximum power | 97.8% | ||||
| Installation | Insertion Frame | ||||
| Loss | Standby <10W, No-load power <100W | ||||
| Dimension(W*L*H) | 586*713*1719 | 586*713*1874 | 586*713*2029 | 586*713*2184 | 586*713*2339 |
| Weight(kg) | 617 | 685 | 753 | 821 | 889 |
| Protection | IP20 | ||||
| Temperature Range | -30~60℃ | ||||
| Humidity Range | 5~95% | ||||
| Cooling | Intelligent Forced Air Cooling | ||||
| Altitude | 2000m (90%/80% reduction for 3000/4000 meters respectively) | ||||
| Certification | Inverter | CE / IEC62019 / IEC6100 / EN50549 | |||